Tech found system 1 not cooling due to a blown 35/5uf dual run capacitor. Tech also found thermostat wire corroded due to sunlight damage. Tech recommends replacing dual capacitor and 6 inches of thermostat wire. Tech let system 1 cool for 10 minutes. Tech found no superheat. Tech recommends thoroughly cleaning indoor and outdoor coils, replacing filter and rechecking R22 superheat and subcooling. System is cooling at this time. Tech found system 9 disconnect in the off position. On further inspection, tech found 25/5uf dual run capacitor miswired. Capacitor is reading in specs. Corrected wiring. Turned power back on and found no Y call. Tech found wire nut connecting float switch disconnected. Float switch tested good, but Y was broken due to missing wire nut. Reconnected float switch and found system back cooling. Tech found system 3 not cooling due to a failed fan motor. Jeff Cupp approved all repairs. No service call on system 3 due to recent repairs per Monica. Tech repaired