Unit #6F unable to access inside of apartment, found reversing valve wiring removed from solenoid. Re-secured wire and system switched over to cooling. O tstat wire for reversing valve looks to have been jumped with R in the past, likely due to issues with thermostat or wiring. System is now cooling, but may not heat unless manually switched at reversing valve. Darryl is aware of situation.