Tech performed CMA full service and replaced filters. Tech found the following issues and gave repair quotes; Blown uv bulb AHU 1 training building Furnace 10 UV bulb is blown, waiting on gas orifices. Furnace 9 zone board temp sensor is reading much lower, can cause issues with locking out on low supply when ac is running. AHU 17 drain pan is cracked ,preexisting issue. Pitted contactor 3a condenser. Out of tolerance capacitor on condenser 2a replaced under contractor warranty Out of tolerance fan capacitor on condenser 16, 4.3/5 Failed condenser fan motor mini split condenser 21. Customer approved replacing zone sensor. This sensor is on the furnace beside the one that needs the orifice repair.