PERFORMED CMA FULL SERVICE ON 2 SPLIT SYSTEMS, 1 GAS PACKAGE SYSTEM AND 2 PACKAGE HEAT PUMP SYSTEMS. SPLIT SYSTEM #1 CONDENSER LOCATED IN BACK OF WAREHOUSE IS IN A BAD LOCATION, CONDENSER COILS WERE EXTREMELY DIRTY, TECH CLEANED COIL AND SYSTEM IS PERFORMING PROPERLY. TECH MEG TESTED COMPRESSOR ON GAS PACKAGE ON ROOFTOP AT OFFICE BUILDING, COMPRESSOR MEG TESTED IN THE CAUTION AREA, COMPRESSOR IS IN ROUTE TO FAILURE, TECH RECOMMENDS PREPARATION TO REPLACE SYSTEM. SPLIT SYSTEM # 2 AT FRONT OFFICE BUILDING HAS A LOW DELTA T OF 13 DEGREES, SYSTEM IS LOW ON R-22 REFRIGERANT, SYSTEM MAY HAVE A LEAK CAUSING REFRIGERATE TO LEAK OUT, TECH RECOMMENDS A LEVEL 3 LEAK SEARCH TO PIN POINT LEAK AREA. THERE IS AN ESTIMATE FOR LEVEL 3 LEAK SEARCH ATTACHED TO THIS INVOICE. CUSTOMER STATED THAT GAS LINES FOR AIR HANDLER #2 AT FRONT OFFICE IS TURNED OFF DUE TO A POSSIBLE LEAK, CUSTOMER WANTS TO GET NEW GAS LINES PUT IN PLACE OF OLD GAS LINES, SOMEONE FROM OUR OFFICE WILL BE CONTACTING CUSTOMER ABOUT NEW G