Today (10/31/25) the hanging unit heater on the west wall had it’s control board and gas valve replaced. The unit was operated after the repair and safety checked. The flue pipe is in good condition and it is drafting. There was no CO detected at the draft diverted and I the airstream. The heater was cycled several time to observe and confirm proper ignition of both the pilot flame and the main burners. Thank you, Jon Quote to replace the failed gas valve and ignition module on the Beacon Morris unit heater serial M99046389006 located on the West wall near the shop door. Price includes the parts and labor. The unit's heating operation will be verified after repairs. Any further repairs if required will be quoted separately.


 .

. Job Checkin

*)*)***(**)*)*)*))*)*)**) Dispatched at 1pm Arrived 1:40 Left 3:25 Closed 3:45 *)***)&))*)*)*)*)&*()*)*)*) Today the hanging unit heater on the west wall next to the shop man door. This unit was not igniting the pilot. The pilot light was cleared and the pilot flame was established. The ignition control board makes a loud bad relay sound and does not pass control voltage to the gas valve to lite the main burners. In addition to this the gas valve’s main valve solenoid windings have failed with a resistance measurement of less than one ohms. The heat exchanger was checked and is in good condition. The fan motor bearings are showing signs of normal wear for the age of the unit but is still functioning. I recommend a new control board, gas valve and a complete pilot removal and cleaning. Thank you, Jon Tech notes: Beacon Morris, m/n BMF-150S//M99046389006 Mv to mvpv <1 ohms Control board does not pass voltage to mv and there is an integrated relay that buzzes when


 .

. Job Checkin

Today (9/16/25). The gas valve in the hanging unit heater (s/n ending 9007) was replaced. This unit heater was checked for proper operation after the repair. The heater enters into heat mode, follows ignition sequence, blower motor cycles properly and shuts down via the thermostat correctly. The flue pipe was also inspected on a previous visit. The heater was left in the off position due to outside temps (lower 90s). The batteries for the thermostat were also changed today and the staff knows how to operate the thermostat when needed. The repair estimate is below for further reference if needed. Thank you, Jon Quote is for replacing the failed fan gas valve on the Beacon/Morris unit heater serial M99046389007 for the Miami County transfer station shop. Price includes the factory parts and labor. The unit could not be fully tested with the gas valve not operating. The full heating operation will be tested after the listed repairs. Any further repairs if required will be


 .

. Job Checkin

Today (9/10/25) the fan motor was replaced. There were multiple wasps nests that were removed during this replacement. The unit did not return to operation after the fan motor was replaced. The unit was diagnosed further and it was discovered that there was no gas entering the pilot tube. The gas valve was receiving proper voltage however it would not open to allow gas through to the pilot assembly. Thank you, Jon Quote is for replacing the failed fan motor on the Beacon/Morris unit heater serial M99046389007 for the Miami County transfer station shop. Price includes the factory parts and labor. The unit could not be fully tested with the fan motor not operating. The full heating operation will be tested after the listed repairs. Any further repairs if required will be quoted separately.


 .

. Job Checkin

*(*)(&)&($)$*)($*()$*$*($( Dispatch at 1 Closed the ticket at 3:30 *)&(($)#*((#*(#**(#*#*( Today the hanging heater on the N.W. side of the shop was checked and found to have a failed blower motor as well as an open limit. The weigh station has a Gree PtAC unit that over runs the internal thermostat. This will be continued into next week due. Thank you, Jon