Rick B.

Rick B. Job Checkin

Checked the Changeair heat pump #16 for too warm yesterday. Found the unit in cooling on arrival with the system at 50% cooling capacity, in dehumidification mode with a 65 deg discharge temp and room humidity 30.9% at a 50% dehumidification enable setpoint. Checked the program settings in the Tracer EMS. Found the active humidity setting "out of service" causing the unit to run in continuous dehumidification mode. Set the active humidity to "in service" and checked operation. Found the unit cooling normal with a 52.1 deg discharge temp at 100% cooling capacity after repairs. Explained the repairs to Larry and Travis.


Rick B.

Rick B. Job Checkin

Checked the Changeair self contained unit #16 for no cool. Found one of three fuses blown to the compressor contactor. Replaced the fuse and started the unit. Verified operation and checked for the cause of the fuse failure. Staff advised that the unit was making a chattering noise before it stopped cooling. Was not able to duplicate the chattering while on site. Bypassed the freeze stat and low pressure switch for testing. Will check back tomorrow the verify operation.


Rick B.

Rick B. Job Checkin

Finished the pm. Emailed Travis Laver a estimate and list of the repairs needed for his approval. Will return tomorrow to start the repairs.


Rick B.

Rick B. Job Checkin

Made the following repairs to the Hvac units after the preventive maintenance. Replaced the blower belts in the East and West units for the Annex gym. Replaced the furnace control board in the Annex unit #5. Repaired the condenser fan wires in the #1 condenser for the Grade school gym. Repaired the condenser fan wires and replaced the condenser fan capacitor in the #2 condenser for the Grade school gym. Secured the condenser fan wires in the #3 condenser of the Grade school gym. Replaced the compressor contactor and made refrigerant leak repairs to HP #16 for the Grade school. Leak searched and made refrigerant repairs to Rtu #29 for the Grade school addition. Replaced the compressor contactor in Rtu #17 for the high school. Replaced the belt with a site stocked spare in the boys locker room exhaust fan for the high school. All repairs were approved by Travis Laver by a email estimate.


Alek A.

Alek A. Job Checkin

Conducted preventative maintenance on AC units. Cleaned all coil. Inspected all electrical and mechanical components. Inspected all blowers, and belts. All repairs have been quoted and submitted for repairs.


Rigo  M.

Rigo M. Job Checkin

Assisted with pma


Alek A.

Alek A. Job Checkin

Conducted preventative maintenance on AC units. Inspected all motors, compressors, blower wheels and belts. Cleaned all outdoor condenser coils. Changed all filters. Check out sheets have been submitted.


Alek A.

Alek A. Job Checkin

Conducted preventative maintenance on AC units. Inspected all motors, compressors, blower wheels and belts. Cleaned all outdoor condenser coils. Changed all filters. Check out sheets have been submitted.


Rigo  M.

Rigo M. Job Checkin

Assisted with pma


Rick B.

Rick B. Job Checkin

Worked on the pm for the complex. Not complete.


Rigo  M.

Rigo M. Job Checkin

Assisted with pma


Rick B.

Rick B. Job Checkin

Checked four Changeair heat pump units #8, #13, #14 and #16 for no cool. Found #16 tripping off on high pressure due to no condenser fan operation. Found the ecm on the condenser fan not receiving the proper 2-10 vdc signal to run. Found the plug in the condenser section for the dc signal failed. Removed the plug and direct connected the wires. Started the unit and verified operation. Found the other three units with the same issue. Removed the plugs and direct connected the wires. Verified operation. Took pictures and sent the failed plugs to the service department at Changeair per their request.


Rick B.

Rick B. Job Checkin

Checked the nineteen Change-air units for the Grade School for burnt wiring harness connections. Found eight plugs burnt at the 460 volt connections. Removed the damaged plugs and direct wired the wires. Made a list of the repairs, took pictures of the damaged plugs and sent the info to Travis Laver as requested.


Rick B.

Rick B. Job Checkin

Checked the high school music room Rtu for no cool. Found the blower belt loose causing poor air flow and freeze stat trippage. Replaced the belt and verified operation. Belt was customer provided.


Rick B.

Rick B. Job Checkin

Checked the Grade school teachers lounge for no cool from the Changeair unit . Found two fuses blown due to a shorted wiring harness going to the condenser fan. Repaired the wiring, replaced the fuses and verified operation. Also checked the Grade school office for no cool from the Changeair unit. Found two blown fuses due to a shorted wiring harness going to the 460 x 240 volt transformer. Repaired the wiring, replaced the fuses and verified operation. The factory harnesses have 460 volts thru the connections allowing arching and fuse failures. Customer requested looking at all 19 units when time allows to check the harnesses for the same issues. Will schedule the requested work.