Checked the Grade school teachers lounge for no cool from the Changeair unit . Found two fuses blown due to a shorted wiring harness going to the condenser fan. Repaired the wiring, replaced the fuses and verified operation. Also checked the Grade school office for no cool from the Changeair unit. Found two blown fuses due to a shorted wiring harness going to the 460 x 240 volt transformer. Repaired the wiring, replaced the fuses and verified operation. The factory harnesses have 460 volts thru the connections allowing arching and fuse failures. Customer requested looking at all 19 units when time allows to check the harnesses for the same issues. Will schedule the requested work.