Customer complaint of no cooling from split system Checked and found thermostat in cooling mode , checked condenser found fan running but no compressor, checked refrigerant charge and low pressure switch both are ok , notice compressor is open on thermal protection, cool down compressor than try to run system ,compressor motors amps locked up about 78 amps, compressor is bad need to be replace, talk with customer and they request to send a quote to have compressor replace All work will be scheduled on condenser unit #3 Trane#3 Model-2TTA0060A4000AA Serial-32112GM3F