Checked 3 ton Lennox split system for no cooling. Found unit low on refrigerant and also noticed oil on the right side of the condenser coil. Located leak with soap bubbles at condenser u-bend connected to discharge line of compressor. At this time the customer wanted us to repair leak instead of replacing coil or system. I recovered the remaining 8oz of refrigerant charge in the system. Solder hole close and pressure test system with nitrogen. The system held pressure for 20minutes, and no leaks were detected at solder joint. Evacuated system and recharged to manufacturer specs. The unit is cooling fine now