Scott w.

Scott w. Job Checkin

Arrived on site to address unit not shutting off. Customer is interested in having positive control over this system. The RTU in question is #2 and serves the back supply / service room (Trane 5Ton s/n: 154112655L) The ReliaTel dehumidification system keeps the fan and compressor running even though the thermostat was turned off. I went through all installer setup options in the Trane BAYSTAT152A thermostat, even resetting all settings to original settings and set the stat up. No changes released control fully to the thermostat until the remote humidity sensor was taken out of the circuit. One wire was cut and taped and left at the sensor in case the sensor is wanted at a later date. The system is now operating the way the customer wants, and is operating properly at this time.


Phil N.

Phil N. Job Checkin

Preventive maintenance. Backflow test and water heater flush. Water treatment room backflow #1 watts lf 009m2qt 1.5” serial# 029415 passed. Backflow #2 watts LF 009m2qt serial #029408 passed. Sprinkler room main backflow LF 009m2qt serial#018728 passed. Flushed water heaters 2 each water treatment room.


Austin W.

Austin W. Job Checkin

The inducer was only getting one leg of power. I checked and tightened the connections now the inducer is getting both 120v legs of power. The unit is heating, I cycled the heat on numerous times with no issues. The mullinax plug is where the connection was lost. The unit is heating as designed at this time.


Doug A.

Doug A. Job Checkin

Upon arrival determined re-occurring issues are being dispatched as service issues, and have probably been addressed but PO’s are submitted for previous services. Spoke with Liz to be able to fix issues with dispatch. No charge visit.


Doug A.

Doug A. Job Checkin

Upon arrival I found multiple ignition failures on small domestic hot water heater, clean flame sensor and re-installed. Cleared faults and tested for operation, set 120. Pro # 3600105329


Jesse R.

Jesse R. Job Checkin

Purchase Order: 3600136384


Gary P.

Gary P. Job Checkin

Performed quarterly inspection and filter change. Inspected heat exchanger, test electrical components, checked motors,belts, and bearings. Found all unit working properly at this time.


Matthew  R.

Matthew R. Job Checkin

Upon arrival found system locked out due to communication failure. Reset system. Checked operation in heating mode. Checked safety’s on systems. System is online and operating properly at this time.


John S.

John S. Job Checkin

Small domestic heater not working , went through heater an diagnosed issue to a bad ignition wire . Other heater isn’t used during summer months , i robbed wire from that heater and installed it on domestic and fired heater up , heater is working fine now . Will order part to replace on other heater next week . Returned 10-4 Installed new transformer wire on heater , tested , all ok.


Cody A.

Cody A. Job Checkin

Completed light maintenance on all units all operating well at this time.


Cody A.

Cody A. Job Checkin

Upon arrival found unit getting call for cooling and control boards showing no error codes but cooling not coming on reset unit and now operating well if problem persists we can speak with manufacturer on replacing control board. Spoke to Jason upon completion of call


Cody A.

Cody A. Job Checkin

Replaced pre filter as bid unit now operating well.


Matthew  R.

Matthew R. Job Checkin

Performed PMA see quote for repairs.