450 Nelms Cir Unit 103
Fredericksburg, VA 22406
(540) 361-6744

Job Locations
for amissville, va


Map of Amissville VA
Trey M.

Trey M.


Job Checkin

During my inspection today, I found a few things I wanted to bring to the customers attention. First being that when I tested the system in heat mode, the burners would not light all the way. After doing some investigating, I found that the third orifice for the burner assembly was clogged. I was able to clear it per membership to get it running for the customer. This was caused by age and corrosion. I am giving the customer the option to replace the liquid propane kit and manifold tube in the manifold tube is on back order and Trane has no idea when it might be in. Customer does want to do this repair. The office will have to keep tabs with Trane on when it will come in. I then found on the outdoor unit that the condenser fan motor is going bad the bearings inside or loose and the motor is over amping . Along with the capacitor which had a mouse on it and caused the capacitor to rust really bad. The capacitor must be replaced with the condenser fan because it is a different size for