Job Checkin

During my inspection today, the customer greeted me at the front door. They then showed me around to the outdoor unit. They explained to me that the outdoor condenser fan motor was not running. I had them turn the system to AC. I went outside and pulled power. I then inspected what I could, and then put power back in the condenser fan motor started running immediately. The compressor was not running though. Upon further investigation, I found that the compressor was out on a high temperature limit. I did not have continuity between run and start. After cooling the compressor down, I was able to get the system up and running. I do not see a reason why the condenser fan motor might be stopping and not working periodically. I am given the customer the option to replace the condenser fan motor seeing as there is a lot of rust on the housing of the motor and it could possibly go down again. Other than this, the system is operating properly and has passed inspection.