Heat rise is 30 degrees. Tested emergency heat and is running well. Supply temp in emergency heat is 116 degrees. Changed air filter. Brushed indoor coil off. Coils have no leaks. Cleaned out water removal system. Indoor voltage system rated 5uf actual is 4.6uf and is within allowable fault. Indoor fan is clean. Secured all wire nuts and connections. Outdoor compressor amps read 7.6 amps. Outdoor fan amps read .6 amps. Outdoor voltage system rated 30/5uf actual is 31.5/4.8uf and is within allowable fault. Operation normal at this time.