Always on time! Rep came out for our winter cleaning and inspection. He took his time and went over our system completely. Great Company to work with!
The tech did a great job. He removed and cleaned the blower that other companies had not done. It now runs smother, quieter and forces more air. Also installed a capacitor that allows the unit to start easier. Start up is now smooth.
Michael and Zach did an awesome job on the install of our new Ac unit. Steve was great at making sure we got the right unit for our home.
Plumbing Repairs: Responding promptly to a client's urgent plumbing concerns, our seasoned team adeptly repaired a leaking pipe. Conducting a thorough diagnosis to precisely identify the leak's source, we replaced the damaged section. To ensure the overall integrity of the plumbing system, we performed a comprehensive check, guaranteeing a durable and leak-free solution.
Returned and replaced the indoor fuel tank gauge with vent alarm.
Vent alarm on tank needs to be replaced.
Gas furnace changed air filter found leak on exhaust pipe at the outlet. There's a leak coming from gasket connecting exhaust removal system to outlet pipe for exhaust. Voltage enhancement factory specs 7.5uf actual 4.89 uf. System is has error code 3 pressure switch open with inducer on recommend replacing switch and control circuit board. Blower is clean heat transfer media coil is good heat rise 51 Condenser voltage enhancement system factory specs 70/10uf actual is 62/8uf recommend replacing below allowable specs, voltage gateway is pitted condenser coil is dirty. Checked all hanging heaters all heaters are normal operation at this time. Cleaned boiler replaced filter and gaskets, replaced nozzle 2.00X70B, replaced screen and gasket inspected combustion chamber. Cleaned chamber sight glass is dirty can't see water level clear inspected flue checked low water cut,-off checked gapping of electrodes bleed and started system. System is functioning at this time
Air Conditioner Repair Service: In response to a service call regarding uneven cooling in the client's residence, our skilled technicians conducted a comprehensive assessment. The investigation revealed issues with blocked air vents and ductwork obstructions, negatively impacting the system's performance. To address this issue, our technicians performed a thorough cleaning of vents and adjusted the ductwork for balanced airflow. This meticulous approach not only resolved the uneven cooling problem but also optimized the overall efficiency of the air conditioning system. To ensure sustained performance, our technicians provided the client with valuable information about the benefits of regular AC system maintenance. The homeowner can now enjoy consistent and balanced cooling throughout their residence, supported by our proactive approach to system optimization and longevity.
Performed club cleaning, checked filter,filter clean. UV light is working. Air movement system is a ECM motor. Checked heat strips, checked voltage gateway are clean contacts are good, checked all electrical connections and harness are tight and secured. Heat transfer media coil system is good. Breakers are functioning as intended. Heat rise 48 degrees Voltage enhancement system 55/5uf actual 54/4.88uf refrigerant pumping system RLA 14.8amps actual 6.06amps outdoor air movement system has ECM motor outdoor heat transfer media coil system is good. Checked all electrical wiring connectors and harness. System is functioning as intended at this time, system is working at this time
Purge oil burner test ran operation normal at this time.
Checked operation of steam boiler. Found system locked out, fuel tank is empty. Oil line will need to have air bled out after receiving fuel. Checked operation of furnace. Found system operating properly. Found filter very dirty, restricting airflow through system. Customer will obtain and replace filter.
WO-TNFR225448, returned and replaced the outdoor safety disconnect, checked pumping system Meg Ohms reading is low, all at 40 Meg Ohms, starting to fail. Removed and cleaned blower wheel replaced the flame sensor and glow bar, test ran.
Warranty, customer wall control was set to 64 degrees, set to 70 and the system started as it should, flame current 2.1 uamps.
No heat gas warm air, main burners are very rusty, installed replacement and test ran. WO-TNFR225417
Furnace Rejuvenation getting a 50 degree heat rise changed filter supplied by customer cleaned burners and flame sensor. No areas of concern at heat exchanger at this time , checked eletrical connections blower and evaporator are clean checked system in ac getting a 18 degree delta t eletrical connections are tight voltage enhancement system read within factory spec Voltage gateway is okay condenser coil looks ok operation normal at this.cleaned boiler changed nozzle and filters and gaskets cleaned cad cell test ran operation normal at this time. Checked fan coil units operation normal at this time
WO-TNFR205119, returned and replaced the indoor air movement system, test run in fan on and heat, operation normal at this point, also drop off 4 pack of media filters.
Warranty, No heat, no A/C, checked system and found that the indoor air movement system has failed, need to return and replace.