Kenneth  C.

Kenneth C. Job Checkin

I installed a new Heil 4-ton 15-seer heat pump with a matching air handler and a 15-kw electric heat kit. I also installed a Honeywell thermostat.


Kenneth  C.

Kenneth C. Job Checkin

I installed a new Heil 4 ton 15 seer heat pump with matching air handler and 15 kw electric heat kit.


Kenneth  C.

Kenneth C. Job Checkin

hvac repair


Kenneth  C.

Kenneth C. Job Checkin

hvac maintenance


Kenneth  C.

Kenneth C. Job Checkin

I was called to a home to find a refrigerant leak in the heatpump system. I used my tools to find the leak and fix it.


Kenneth  C.

Kenneth C. Job Checkin

I installed a new Heil 60,000 btu 96 eff propane furnace.


Kenneth  C.

Kenneth C. Job Checkin

I installed a new Heil 60,000 btu 96% eff propane furnace.


Kenneth  C.

Kenneth C. Job Checkin

Responded to emergency no-cooling call for elderly resident. Upon arrival, indoor temperature was 88°F. Diagnosed failed compressor in 10-year-old 2.5-ton split system. Compressor windings showed open circuit on ohmmeter test. Discussed replacement options with family member. Installed temporary 1.5-ton portable AC unit to provide immediate relief. Returned next day with new 3-ton 16 SEER system. Replaced both indoor and outdoor units. Upgraded from R-22 to R-410A refrigerant. Installed new line set to prevent contamination. Recharged system to 7.5 lbs per manufacturer specs. Verified proper operation: superheat 12°F, subcooling 11°F. Supply air temperature 53°F with 20°F delta T. Adjusted airflow to 400 CFM per ton. Programmed new Wi-Fi thermostat for optimal comfort and efficiency.


Kenneth  C.

Kenneth C. Job Checkin

Today, I responded to a service call for an AC unit that wasn't cooling. Upon arrival, I conducted a diagnostic which revealed a tripped circuit breaker and a blown capacitor. After resetting the breaker and replacing the capacitor, I tested the system for functionality. The airflow and temperature output are now stable, ensuring the unit operates efficiently throughout the season.


Kenneth  C.

Kenneth C. Job Checkin


Kenneth  C.

Kenneth C. Job Checkin


Kenneth  C.

Kenneth C. Job Checkin


Kenneth  C.

Kenneth C. Job Checkin


Kenneth  C.

Kenneth C. Job Checkin


Kenneth  C.

Kenneth C. Job Checkin

Service call: air conditioner isn't working. upon arrival found the filters and coils were dirty due to lack of maintenance. that had caused the ac unit to malfunction. recommended maintenance plan to prevent these issues in the future.