Commercial plumbing water heater repair. Estimate to replace Taco circulating pump in administration mechanical room.
Commercial ductless HVAC unit service. Tested system, checked compressor on Daikin’s split and multi-split type air conditioning systems.
Ice machine repair. When I arrived the ice machine bin is full of ice, I believe the plastic curtain was stuck open. Where it drops ice into the bin I took photos of the ice and the plastic curtain I showed Joel where the Curtain is location just in case it sticks again.
ESTIMATE TO SANATIZE AND DE-LIME ICE MAKER
ESTIMATE TO REPLACE 3 WAY VALVE FOR NORTH DORM
Commercial rooftop HVAC system repair. #1 R/A damper on this unit is closed when building system is calling for it to be opened at 100%. I had them override system and lock it at 0% this motor closed and dampers opened 100%. This damper needs to be flipped so it works correctly. #2 found 3 way valve with linkage all disconnected the system was saying 100% heating but coil was cold. Remove power head (motor) and manually open valve to get building to heat. Building is heating as of now but not controlled by automation system.
Commercial boiler service. Go to job found supply and return line air locked bleed air from system. Let run awhile had control guy raise water temperature for boiler to low 150 off 110 on . Also let them know to check glycol in make sure it is good . System is running . IT guy is adjusting set points for system.
ESTIMATE TO REPAIR / REPLACE LEAKING PUMPS IN SOUTH DORM ROOM
ESTIMATE TO PERFORM ANNUAL PREVENTATIVE MAINTENANCE ON (3) COMMERCIAL WATER HEATERS
ESTIMATE TO SANITIZE AND DE-LIME ICE MAKER
ESTIMATE FOR PREVENTITIVE MAINTENANCE ON (2) COMMERCIAL WATER HEATERS FOR THE SOUTH DORM
Commercial plumbing repair. Found leak from trap primers for shower and floor drain. Replaced two 1/2” trap primers under lavatory sink in room 164 of south dorm. Blew out primer lines with CO2.
COMMERCIAL HVAC SYSTEM ESTIMATE TO REPLACE BELIMO CONTROL
Checked oven, main thermostat controller only turns on at 400 degree, suggested replacement of control knob and sensor. Estimate for this work will be provided.