467 Ruby St
Joliet, IL 60435
815-726-6264

Job Locations
for crest hill, il


Map of Crest Hill IL
Brennon E.

Brennon E.


Job Checkin

Air conditioner repair. No ac call. Found blower motor barely working. Tested blower motor capacitor and that was still good. Tested blower motor amperage and indicated blower motor was bad. As I was testing blower motor, motor came to a halt. Replaced blower motor with a 1/2 hp universal motor. Washed out fan cage and housing while having it out of furnace. Customer signed up for annual VIP maintenance program. Customer used one visit now for the condensing unit. Cleaned, washed out and serviced condensing unit. Tested capacitor, contactor, fan motor amperage and compressor amperage. Found the unit to be extremely dirty. After system was cleaned found capacitor extremely low on compressor side and empty on fan side. Replaced using a 45/5 mfd capacitor. Checked r410a refrigerant and it was at accurate efficiency range. Customer will have one more visit for this 2024 fall season. Furnace is a 90% Trane from 2003. Ac was replaced in 2015 by us. Amana condensing unit.