Heating repair. Low heat call out. Customer stated that thermostat said that it had been running for two hours. Upon detailed inspection found the pressure switch to be intermittent. Vacuum started at -1.30 then reduced to -1.00. Pressure switch at -.60. Replaced pressure switch and hose.