Contacted resident Went to attic Performed spring PM Found blower cap out of specs 5 -+5% low would be 4.75 Their cap was 3.8 Recommend replacing capacitor- Replaced capacitor Compressor amps were 6.5 rated 14.1 good Condenser amps were,66 rated 1.0 Supply air was 46 Return air was 69 Split of 23 Unit now running at manufacturer specifications