Checked in with customer Pulled (2) 20x25x1" filters from TS-113 and set on porch Started with East unit serial # 1715C07070 Checked electrical, 245.3v high, 28.9v low Checked contactor for putting, visual inspection, no burn anywhere Checked capacitor (35-5uf) good Checked all board connections for any loose items in wiring Checked transformer setting for 230v high Checked inducer fan motor, found motor not coming on Continued check from inducer pressure switch, rollout switch, high limit switch And found wire connector off at bottom of switch Tightened and connections inside fan compartment, no loose connections now Put unit in heating mode, verified inducer and blower fan operation Inducer at .56 amps & .57 amps, good Checked indoor evap coil for any leaks with sniffer, no leaks found. verified clean Using camera, checked heat exchanger tubes and baffels. Cleaned out with blower. Blew out electrical and blower compartment Verified proper operation and visual inspec