Contacted resident, no one home Left filter on porch Went to roof Cleaned electric compartment Checked compressor amps 10.1 rated 14.8 Condenser amps 1.0 rated 1.6 Checked dual capacitor 45+5 Herm 44.9,good Fan 5.1, good Temperature rise Supply 100° Return 75° Rise of 25,good Unit running as per manufacturer's specifications
Customer called and wanted quote on a new unit- One of the bedrooms was getting too hot Checked in with customer Took measurements for new unit Provide information to supervisor Will provide quote for new unit Job complete
Checked in with customer Removed condensate, electrical connections and labeled. Completed demo of unit, Installed new 2.5 ton Coleman heat pump with heat strips and adjustable curb. Start and test. Job Complete