Responded to no heat. Furnace shutting off after startup. Found flame sensing system charred providing weak signal. Presented hm15 a-e customer chose option a. Opted to not sign up for maintenance but will call when wanting to replace. Performed repair. 65 degree deltat. Cycled furnace multiple times to ensure operation. 5.7%o2. 10 ppm co in flu.