Matt P.

Matt P. Job Checkin

Capacitor in condenser is out of range, should be 45uf plus or minus 6% and is reading 35uf. Blower motor capacitor should be 10uf plus or minus 6% and is reading 7uf


Pete L.

Pete L. Job Checkin

System has a 10 degree split, this means the system is working at 50% efficiency. Unit has a major restriction in the filter drier which is causing an extremely high head pressure and will cause damage to the compressor or lead to a leak. The unit was also very overcharged with Freon, I believe a technician must have come out and saw the pressures off and thought it was low on refrigerant when it was the restriction causing the unbalanced pressures making it look like it had low refrigerant. Recommend pumping down system, extracting over charged Freon, flushing system and replacing filter drier.


Matt P.

Matt P. Job Checkin

Diagnosis


Joseph S.

Joseph S. Job Checkin

System has a 10 degree split, this means the system is working at 50% efficiency. Unit has a major restriction in the filter drier which is causing an extremely high head pressure and will cause damage to the compressor or lead to a leak. The unit was also very overcharged with Freon, I believe a technician must have come out and saw the pressures off and thought it was low on refrigerant when it was the restriction causing the unbalanced pressures making it look like it had low refrigerant. Recommend pumping down system, extracting over charged Freon, flushing system and replacing filter drier.


Pete L.

Pete L. Job Checkin

Check blower motor and amperage checked all ductwork check primary drain line and secondary drain line checked all electrical connections check temperature differential checked condenser fan motor amps and compressor amps check capacitor check Freon levels found Freon level low homeowner did not want leak search or Freon added at this time


Alex T.

Alex T. Job Checkin

Installed 2 Ductruns, Boxes & Grills.


Alex T.

Alex T. Job Checkin

maintenance: performed heating maintenance on gas furnace. Heater is achieving 42 degree temperature rise. Duct work is showing signs of age, losing efficiency from heat and cold penetration. Recommend replacing duct work for more efficient unit operation.


Joseph S.

Joseph S. Job Checkin

Power surge caused shorting of electronic board & additional devices, items beyond this point cannot be tested until these components are replaced and could lead to additional charges. Sealing of unit recommended to reduce air leakage & Carbon monoxide motor.


Alex T.

Alex T. Job Checkin

Ac repair: replaced gas shut off valve for furnace, negative pressure switch, and flame sensor rod. Furnace flame is solid blue and consistent. Heating normally at this time.


Matthew J.

Matthew J. Job Checkin

Ac repair: contactor had burnt up on the neutral side. Re paired the wires that were damage and ohmed out the compressor and fan and they showed no signs of damage. Replaced contactor and took amp readings for the compressor and fan motor both were in range as well. Recommend installing a surge protector in the future.


Matthew J.

Matthew J. Job Checkin

Ac repair: fan motor was not spinning up due to a capacitor being out of range. Swapped out capacitor just to get it running and noticed the bearings in the motor and going out. Motor was making squealing sound and is showing signs of beginning to cease up. Replaced motor fan blade and capacitor. Unit is now up and running properly.


Alex T.

Alex T. Job Checkin

Call back: wire was loose again. Cut wire back and changed connection to ensure snug fit. Gave wire a considerable tug to make sure connection would not come loose. Jostled and shook all the wires to verify there were no shorts or opens in the wiring to the unit.


Alex T.

Alex T. Job Checkin

Ac repair: high voltage wire in furnace was loose, secured wire and system is operating normally. Achieving 16 degree temperature split at this time.


Matthew J.

Matthew J. Job Checkin

Home warranty: unit was not cooling properly. System pressures were low indicating a leak in the system somewhere. Next step is to conduct leak search. Contacted AHW and they said they were not going to cover the leak search so the customer would have to pay out of pocket. Customer would like quote from mr Joseph for replacement options.


Alex T.

Alex T. Job Checkin

AC Repair: return duct was open to attic space pulling in attic air. Sealed return plenum with matrix tape and system is achieving a 17 degree temperature split. The outdoor coil is corroded due to age and high side pressures are starting to rise. Recommend replacing filters at the returns for best airflow.