Fine tuned energy monitoring for both units. Went through start up on each unit. Set 7 Series blower speeds to correct settings, set flow rate and recorded heat of extraction. Setup the humidifier to operate from the thermostat. Pressurized the ground loop to 65psi. I had to secure the blower cabinet insulation with some elastomeric compound because there was almost no glue applied from the factory and it pulled away when I removed the cabinet door. I checked the electrical wiring and electrical systems including the auxiliary heat strips, all are within specification. I set the flow rate on the 5 Series split system and recorded heat of extraction. I increased blower speeds very slightly to keep temperature rise across the air coil to <30 degrees. Both units are operating normal. I removed the valve handles from the geo water piping and placed them on the respective flow centers. Customer awaiting 2) Symphony WiFi systems. The office is aware and asked me to tell the customer that