Fall pm on 01/10/20 On arrival I sanded the flame rectification probe and checked burner arrangement the ignitor homes out to be in good condition checked all other electrical connections set unit #1&2 to call for heat measured supply and return air temp measured voltage and amps inspected electrical connections checked drain cleaned checked filter and replaced checked blower motor checked all other electrical connections checked temp rise unit #1 DT 70.5 degrees made for 45 to 75 unit #2 DT 60.7 temp rise made 40 to 70 degrees to unit tested unit operating normal at this time checked unit #3 heat pump set unit to call for heat measured supply and return air temp measured voltage and amps inspected electrical connections checked drain cleaned checked air filter checked blower motor checked coil checked condenser unit outdoor checked electrical connections checked voltage and amps checked compressor capacitor checked all other electrical connections checked pressure and temp unit has


Daniel S.

Daniel S. Job Checkin

Inspected units in heat test mode to verify proper operations. Inspected motors for proper rotation and amp draw. Took temp reading. Found both units to be running good. Unit 1 has a rusty exchanger looks to be very old no cracks found unit is running good. Job complete


Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com Job Checkin

When I arrived I checked thermostat called for heating check all logical components wires amperage checked airflow delta T1 20 return 75.5° OK for options even though the customer was in a rush to get to work I filled out a follow-up form to see when customer will be ready to get estimate options done I gave a few more recommendations on tasking maintenance sheet.Heat working and draft motor that was installed not long ago working.


Joseph.Wade@supremeairllc.com

Joseph.Wade@supremeairllc.com Job Checkin

Up on arrival performed heating maintenance. Changed all filters ( 16x25x2 ) and belts ( ax32 ) checked units for operation. All units working good at this time


MarkM@supremeairllc.com

MarkM@supremeairllc.com Job Checkin

Completed the spring maintenance. Checked the wiring and connections. Replaced the air filters. Checked the blower belts. Cleaned the drain pans and traps. Cleaned the condenser coils. Checked the units operation.


Yonas M.

Yonas M. Job Checkin

Inducer motor replacement on arrival take out the old inducer motor out put the new inducer motor fixed tested checked electrical connections checked voltage and amps measured supply and return air temp unit operating normal at this time on heat. Collected the balance $461.00 Same C.C on file.


Yonas M.

Yonas M. Job Checkin

York Gas Furnace inducer motor repair Elkton Md

York Gas Furnace inducer motor repair Elkton Md

Colin T.

Colin T. Job Checkin

Performed ac pm on both rooftops. Cleaned condenser coils. Replaced filters. Inspected belts, blowers, and Evap coils. Flushed out drains. Checked capacitors and contactors. Tightened electrical connections. Ran ac. Checked amp draw of compressors, od fans, and blowers. Measured delta air temps at all coils. Let systems satisfy thermostats. Units are operating normal at this time.


Colin T.

Colin T. Job Checkin

Performed ac pm. Replaced all filters. Flushed out all drains. Inspected all coils and blowers. Checked capacitors and contactors. Tightened electrical connections. Ran ac and checked operation. Measured amp draw of compressors, od fans, and blowers. Checked delta air temps at both coils. Let systems satisfy thermostats. Units are operating normal in ac mode. Customer explained that HeatPump froze over the winter but they didn’t call for service, just shut it off because they won’t use it much. Found unit not going into Defrost manually or automatically. Outdoor ambient and defrost sensors are connected to board and cannot be removed. Quoting customer to replace Defrost Board with Sensors. Customer would like to have heating pm done on 10/17 if possible. Please follow up with customer to confirm.


Yonas M.

Yonas M. Job Checkin

Spring Pm On 04/05/19 On arrival set unit to call for cooling measured supply and return air temp measured voltage and amps inspected electrical connections checked drain and cleaned checked filters cleaned also checked condenser unit checked electrical connections checked voltage and amps checked capacitor checked coils also customer have problems with heat he was call office last week I checked his heat set unit to call for heat checked electrical connections checked voltage and amps I found the inducer motor is burn I gave quote for customer accepted order the parts we have to come back to finish the job also the unit need multiple parts and cleaning my recommendation blower motor needs to be cleaned duct work outdoor condenser run capacitor is weak the compressor contactor is burnt I talk to Mr Steve but he has plans to sell the house he don’t want to replace the unit he needs to us fixing the heat for him. I collected $461 on the card on file.


Yonas M.

Yonas M. Job Checkin

York Gas Furnace spring Pm Elkton Md

York Gas Furnace spring Pm Elkton Md

Colin T.

Colin T. Job Checkin

While testing unit 1 after replacing heat exchanger I inspected unit 2 because customer mentioned that it was overshooting setpoint. I found system was satisfying thermostat properly. Checked heating operation. Measured heat rise and amp draw, checked gas pressure and cleaned flame sensor. Speculating space heater possibly adding heat and increasing indoor temps. Unit operating normal.


Colin T.

Colin T. Job Checkin

Upon arrival I went to roof and started removing panels. Removed inducer and manifold to get to heat exchanger. Removed heat exchanger and installed new one. Then installed bracket for blower assembly so it doesn’t wobble. Ran fan only and verified quiet operation. Restarted unit and ran heat. Unit shutting off on high Limit, first stage heat. Found gas pressure at 2.3 inches, rated for 1.6 inches in first stage. Lowered to spec. Ran second stage and found normal gas flow rate. Checked heat rise and amp draw. Unit operating normal at this time.