3100 39th Ave North
St. Petersburg, FL 33714
727-822-7700

Job Locations
for dunedin, fl


Map of Dunedin FL
Jeff B.

Jeff B.


Job Checkin

No cool Found system low on 410a refrigerant. Rechecked pressures after 10 minutes and pressures continued to drop indicating the system was freezing. Found oil in drain line indicating a leaking evaporator coil. System is a Frigidaire mixed coil system these systems are prone to evaporator coil leaks. Refilled the system for temporary cooling. Homeowner is aware that the system will continue to leak until replaced or repaired. I discussed repair versus replace on a 10 year old system with no warranty. He would like a quote for both so he can decide how he would like to move forward. Office to build repair quote and call to set an appointment for our comfort advisor to come by. System is cooling at this time. Model b6bmm036kb Sn. B6d130117270