3100 39th Ave North
St. Petersburg, FL 33714
727-822-7700

Job Locations
for gulfport, fl


Map of Gulfport FL
Arionna L.

Arionna L.


Job Checkin

Called out today due to no cooling. Upon arrival air handler was running but the condenser was not. The contactor was so heavily pitted that it would not allow power to pass through the condenser. Since the condenser was not running the machine was not able to remove heat from the home. Educated client on the importance of annual maintenance as well as member discounts on trip, repairs and replacement. Enrolled in maintenance agreement and replaced contactor. Checked electronics and motor components to ensure equipment is operating within manufacture specifications. Capacitor was within tolerance, refrigerant pressures were okay and the amperage was within specs at the condenser. However the air handler had an abundance of bacterial growth which is impacting the airflow through the evaporator coil and putting stress on the blower motor. Client is fully aware that the machine is 18 years old which can and will fail at any time. He would rather invest into repairs than replaceme