Used IFLO Pro device and bottle of formula ! Customer purchased membership per Collin on 9-26-2024. Upon arrival found system off on the float switch. Flushed drain assembly and installed IFLO pro device with formula bottle upon approval. Checked pressures, temperatures, and amp draws. All within factory specifications. System is working and draining properly. Will need to replace formula bottle for IFLO PRO every 6 months. - Collin