Called out today due to no cooling. Upon arrival client stated that the unit stopped blowing cold about two days ago. I checked all electronics and motor components. I found that the condenser would not turn on although the correct power was being sent outside. Inspected defrost board and found a lizard burnt to the terminals. This machines warranty ended in march of 2022. I gave options for preventative maintenance plans and repairs. Client declined preventative maintenance and chose a one time repair. Installed new defrost board and sensors. Tested system operation. Checked refrigerant pressures. Measured the temperature drop across the coil. Drain line is heavily impacted due to inaccessible clean out. Clogged drain lines lead to breakdowns. Filter is heavily impacted. Condenser coil is impacted and is in need of cleaning. System is operating at this time. Thank you for always choosing Total Air!