Maintenance 1 Completed first maintenance for a strait cool split system. Checked all electrical components for proper volts and amp draw. Found blower capacitor slightly off 5 percent capacity. ( .35 ) low. Dual capacitor tested ok. System pressures are at the correct levels. System is 18 years old and runs r22 refrigerant. System split temp are normal. Unable to clear drain. The drain is communal and does not have a clean out tee. Recommendations: 1 uvc light and blower compartment cleaning. System had a small amount of growth. Growth should be cleaned and uvc light installed to prevent growth from returning. 12.5 blower capacitor should be replaced. Due to age of the system a hard start capacitor can prolong the compressors life span and smooth start up. Condensate drain line does not have a clean out tee. PVC should be rebuilt to allow regular cleaning and allow vinegar to be added. System operating normally at this time