Arrived at customers house for noisy unit. On arrival customer showed me to condenser. Open electric cabinet. Checked all components. Unit had proper voltage. Sending from contactor. Capacitor was below nameplate rating but within acceptable range. As an attempt to isolate and see whether it was specifically the fan or compressor. Making the sound a disconnected power to compressor. Customer and myself no longer heard sound. Went into condenser and tested compressor. Compressor windings are fine. Unit does not feel warm. Attached power back to compressor. Started up unit. Unit started fine electrically. had aunt meter connected to compressor. While running compressor appeared fine. Fan was fine. Hooked up gauges and all readings looked fine. Only thing I noticed was surge. Protector was non-functional. Unit could have had a tiny surge that caused some sort of change electrically. suggested customer get new surge protector. explain to customer what was going on and customer is comforta