Water furnace premiere short cycling on low pressure switch Leak repair at capillary tube joint on suction line Brace over existing joint and pressure test at 65 PSI Evacuate to 500 microns and recharge R22 system running at 53 and 190 in heat mode Minor maintenance shop vac cleaning and drain flush Water furnace premiere 2 second system in the basement, Minor maintenance cleaning, Shop-Vac evaporator coil, run test two-stage heating and thermostat, power flush condensate drain, pressure test ground loop circuit. One two pump flow center and one outdoor ground loop feeds two geothermal systems in the basement ***Auxiliary electric backup heat has broken coils on both air handler systems electric heat was not tested on either piece of equipment homeowner says electric heat is not necessary Homeowner will service washable air filters. no water access due to freezing outdoor conditions today