They did a fantastic job installing my Waterfurnace geothermal unit. Very efficient! Thanks guys!
WaterFurnace geothermal maintenance and performance test. 5 Series NDV038 22,300 Heat of extraction at 30 deg water temp. Providing a COP of 3.8. That is 3.8 times more efficient than electric heat.
Warranty diagnostic on Daikin mini split heat pump The warranty replacement coil that was changed in October is leaking in the exact same spot as the original coil.
Install new Daikin HVAC system Heat Pump: DZ6VSA3610 Serial: 2303195157 Air Handler: DFVE36CP1400A Serial: 2403224520 15W Heat Strip: HKTSD15 Daikin One communicating thermostat: DTST-TOU-A Serial: EA2404018426 * 1" Filter Standard Filter Rack * Install high voltage electric to indoor and outdoor units * Fix ductwork - Install one 14x8 end cap and one 6" heat run to bedroom * Reconnect to existing gas line and high voltage electric * Transition to existing supply and return ductwork * Start up and commission new system 12 Year Daikin manufacturers parts warranty (Annual maintenance must be performed) 2 Year Westin Air labor warranty (Annual maintenance must be performed) Lifetime Heat Exchanger Warranty (Annual maintenance must be performed)
Daikin single zone mini split heat pump almost out of refrigerant Performed visual leak search All flare fitting connections in the line set are dry and clean Saw no signs of oil on indoor or outdoor coils Added refrigerant and dye System cooling normally As I was packing up my tools and the unit was off, I heard hissing Used soap bubbles to locate a leak on the outdoor coil Will need to replace the outdoor coil under Daikin factory parts warranty. Replaced outdoor coil. System operating normally at this time. .
2004 Bryant 90Plus furnac3 converted to propane is running in good condition despite age. 16x25x4 air filter is new today. Used homeowner supplied filter but left new filter included with gold plan next to furnace. Clean flame sensor and check ignitor. Visual inspection of burners, no rust visible. Flushed collector box and condensate trap. Tested system in EM-Heat mode from Vision Pro 8000 thermostat. Tested flame sensor and pressure switches. Inducer motor tested at 0.45A, rated at 0.75FLA. Blower motor is operating at 7.05A and blower capacitor that was replaced recently is reading within spec. 2" pvc flue in good condition and no sign of leaks. 0PPM CO detected during testing. Delta t of 47F with supply temp of 115F, spec Delta t of 30-60F. Data on propane inlet pressures are as follows. With nothing running, inlet pressure is 11.9inwc. With stove and generator running, inlet is 4.5inwc but slowly rose to approximately 6.5inwc. With generator only running, inlet is at 11.6inwc, a
Diagnostic on a Daikin mini split heat pump system. Single zone, 24,000btu (2 ton).
Daikin ductless heat pump installation.
Daikin Systems Installed for a customer near Apple Valley.
Three single head daikin ductless mini split install.
Properly disposing of your old HVAC equipment
Waterfurnace geothermal heat pump quote.
Installing Waterfurnace 7 series geothermal heat pump in new construction home near Mt Vernon.