Performed maintenance on Daikin Fit dual fuel system Corrected an issue with the inducer clamp that was leaking water Pulled and cleaned flame sensor Went through thermostat settings. No relevant fault codes Run tested furnace and heat pump 17 degree temp rise with heat pump 48 degree temp rise on high heat for the gas furnace Filter is new All sounds/noises from the equipment are normal.