Brandon P.

Brandon P.


Job Checkin

2016 Trane furnace running in good condition. 16x25x1 air filter is new today. Clean flame sensor and check ignitor. Visual inspection of burners. 4" galvanized B-vent in good condition and no sign of leaks. 0PPM CO detected during testing. Test ran system in heating mode from thermostat. Delta t of 45F with supply temp of 114F, spec Delta t of 30-60F. Inducer and blower motor tested within spec. System is operating properly, efficiently and ready for Winter.