2009 Lenox electric air handler with 20 kW electric auxiliary heat and 4 ton outdoor heat pump Vision pro 8000 April Air 400 series (#12 water panel) humidifier Install replacement washable air filter supplied by homeowner, visual and physical inspection of evaporator coil and blower system. Water flush indoor coil drain pan, hot wire inside air handler to test run water flow through solenoid valve and saddle valve of humidifier. Confirm operation of all four heat strips. Circuit 1 - 35 amps circuit 2 - 46 amps Outdoor unit run test in heat mode Outdoor coils are good, starting relay is original but in good condition power supply is replaced last year with 5-year warranty, control board is functioning properly, refrigerant pressures are within acceptable levels in heat mode 122/417 165°f discharge line temp Indoor and outdoor equipment is running in very good condition and ready for winter. homeowner settings on humidistat and thermostat controller we're not adjusted equipment