725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Job Locations
for sunbury, oh


Map of Sunbury OH
Nate G.

Nate G.


Job Checkin

Two Carrier rooftop gas fired units. Front of house required a new belt. System was locking out on successive limit trips due to insufficient airflow from the worn out belt. This unit is in need of a new heat exchanger and inducer. Extremely rusted out and has pin holes. Back of house unit had the gas valve shut off internal to the unit. Heat exchanger is in OK condition for now, but will need replaced in the near future.