Customer had lights dimming when microwave was turned on. Tested amps pulled by microwave(9amps). Tested voltage at main lugs(240v). Tested voltage for each leg without load( 120v, 120v). Tested voltage for each leg with load(~150v, ~90v). Determined there was a loose neutral coming from power company.