The reason for today’s visit with customer was a continuously tripping breaker for the garage/outdoor plugs. After arriving i was taken to the garage where i saw a 200 amp Homeline panel installed in 02. The panel had multiple shared neutrals/double taps/ and a shared circuit. After inspecting the panel, i checked the integrity of the exterior outlets where i saw both had water damage/Mulberry flapper style covers that was allowing moisture to set in. After inspecting the outlets i began assessing why the breaker was tripping with the mower. The mower was an electric 12 amp plug in style mower. I plugged it into the garage then into the living room outlets and saw it was still causing a trip. I then plugged it into the washer outlet which was a 20 amp circuit and it caused a trip there as well. After seeing the washer outlet i recommended on GFCI protection due to device being within 6 ft of water. After testing the mower in multiple locations and testing the circuits i made my recomme