Job Locations
for university park, md


Map of University Park MD
Alex W.

Alex W.


Job Checkin

When I originally came out to check a power outage in the office I noticed that the receptacles were backstabbed when I went down to check the electrical panel and the breaker they kept tripping when I took the panel cover off I noticed that there was a 150 amp SEU cable powering a 200 amp electrical panel after making my discoveries I presented the options to the customer and he decided to move forward with the upgrade option So I installed a 200 amp SEU cable with a new weatherhead going down customers wall outside which will be connected to the powerlines from Pepco I installed a new meter can. I removed the 150 amp SEU cable from the electrical panel and pulled it outside thenI installed a new 200 amp SEU cable from the meter can into the electrical panel. After that I temporally bugged the old SEU cable and the new SEU cable together to power the customers homes Pepco will make the final connections into the meter can after we pass inspection. When doing this we have to bring e