Annual alarm inspection Per Christie Hunter needs to be scheduled on a Mon/Wed/Fri Alarm Systems Inspection
Annual fire sprinkler inspection Sprinkler Inspection
Annual Fire Extinguisher Inspection (All 10lb & 5lb Extinguishers are due for SY in 2018) BRC ID: 700894 Portable Extinguishers Inspection
Annual fire extinguisher insepction Portable Extinguishers Inspection
Sprinkler Inspection 3 Year Full Trip Test on Dry Sprinkler System Annual dry sprinkler inspection Inoperable Deficiency: Small wooden building in corner of warehouse has covered ceilings and no sprinkler coverage. Dry System has alarms that are not connected to any bell nor alarm panels. Control Valve is not locked nor supervised. System will be Yellow Tagged.
Sprinkler Inspection 6 N/A: Annual Sprinkler Inspection Inoperable Deficiency for 6 N/A: Dry System is due a 5 Year Internal Obstruction Investigation and Gauge Replacement x2 (2013).
Swap out all Strike First extinguishers. Bring an additional 5lb ABC extinguisher
Portable Extinguishers Repair (39) 5lbs Fire Extinguishers are due for 6 year Service. (1) 2.5lbs Fire Extinguisher needs to be replaced to be complaint (plastic head currently in place). (9) 10 lbs Fire Extinguishers are due for 6 year service.
Sprinkler, Backflow, Alarm Systems, and Portable Extinguishers Inspection Annual Sprinkler Inspection (2) Annual backflow inspection for two devices (2) 1) Ames 2000B 2" SN# 30675 Location: Fire sprinkler riser Bldg D 2) Ames 2000B 2" SN# 30673 Location: Fire sprinkler riser Bldg E Bosch FPD-7024 Electrical Room - Buildings D & E: Annual Fire Alarm Inspection Annual Fire Extinguisher Inspection (All 10lb & 5lb Extinguishers are due for SY in 2018) BRC ID: 700894 Inoperable Deficiency: 39 5lbs Fire Extinguishers are due for 6 year Service. 1 2.5lbs Fire Extinguisher needs to be replaced to be complaint (plastic head currently in place). 9 10 lbs Fire Extinguishers are due for 6 year service. Need a quote to do services
Backflow, Sprinkler, Portable Extinguishers, and Alarm Systems Inspection Annual backflow inspection (3) 1) Watts 007M1QT 2" SN# 18966 Location: Fire sprinkler room Bldg B 2) Watts 007M1QT 2" SN# A21590 3) Watts 007M1QT 2" SN# A21602 Location: Fire room riser Bldg A Annual sprinkler inspection (2) Annual portable extinguisher inspection BRC ID: 700895 Annual alarm inspection
Kitchen Suppression Inspection Semi-Annual Kitchen Hood System Inspections
Conducted quarterly sprinkler inspection
Conducted quarterly sprinkler inspection