1121 Grassdale Road NW
Cartersville, GA 30121
770-334-8713

Job Locations
for dahlonega, ga


Map of Dahlonega GA
Bert P.

Bert P.


Job Checkin

The quote below is for the Annual Alarm Inspection of different systems: Alarm Systems Inspection Annual Alarm Inspection (Edwards) (2-systems) Inoperable Deficiency: Upon Arrival FACP appeared to be normal and LED Was functional. Upon opening panel door the screen went blank. Checked all wiring and all was correct and connected. I set off several fire alarm devices and FACP acknowledged it but would not read on screen, as far as location and type of device. Signals did go to Monotoring station. If a fire device goes off location and type of device will not known. System will be red Tagged. Particular panel model is no longer made. Spoke with management and they advised that they had the same problem and panel screen was replaced.