1121 Grassdale Road NW
Cartersville, GA 30121
770-334-8713

Local Reviews
for franklin, ga


Job Locations
for franklin, ga

Luis M.

Luis M. Job Checkin


Luis M.

Luis M. Job Checkin


Bert P.

Bert P. Job Checkin

Annual inspection of portable fire extinguishers Portable Extinguishers Inspection


Troy L.

Troy L. Job Checkin

Alarm Systems Service Call


Luis M.

Luis M. Job Checkin


Luis M.

Luis M. Job Checkin


Luis M.

Luis M. Job Checkin

Downgraded micro codes. Tested Proinert. Will need to be back tomorrow to seal all conduit and seal all pull stations in Plant.


Luis M.

Luis M. Job Checkin

Bypassed CRH going to the T300 for the Turbine Trip. Closed the contacts so the T300 could be at its normal state. Spoke with Robert about the relay, so we could rule out if it’s a Card or relay issue. Contacted EST about the timing issues and was told they are still working on it. Will need to be back out here Wednesday afternoon to check status of T300. Will also need to bring the locks to replace existing ones.


Luis M.

Luis M. Job Checkin


Troy L.

Troy L. Job Checkin

Replace the existing silent knight 5207 fire alarm panel.


Luis M.

Luis M. Job Checkin

Responded to Duct Detector Alarm in Men's Restroom. Arrived on site checked Duct Detector filter is clean. Adjusting sampling tube. Cleaned out Duct Detector. Panel normal upon departure


Luis M.

Luis M. Job Checkin

Arrived on site went through history found Ground Fault on Low Pressure on Bottles on Unit 2. Found wire moist with condensation. Taped wire and siliconed wire to avoid future problems.


Luis M.

Luis M. Job Checkin

Upon arrival panel had Unit 2 Electrical Package OFF BOTTLE Trouble. Went to unit 2 EP checked wires with meter. Reterminated all connections. Went to Unit 2 Excitation. Could not get Module to clear. Replaced module, check wired with Meter. Panels have 2 Troubles upon departure. (Panel 3 and Panel 4)