Edwards EST 2 Electrical Room: Annual inspection of Fire alarm system in the Admin building Annual inspection on (5) Chemetron CO2 systems covering CT Generators - Annual inspection and maintenance of Refrigeration units on (4) low pressure CO2 tanks - Alarm Systems and CO2 Suppression Inspection
Verify with Greg for Dec inspection dates if the refrigeration units need to be inspected or if he still wants this on hold. Alarm Systems and CO2 Suppression Inspection Edwards EST 2 Electrical Room: Annual inspection of Fire alarm system in the Admin building Annual inspection on (5) Chemetron CO2 systems covering CT Generators Units 1-3 11/1-11/2 Units 4-5 12/3-12/4
Portable Extinguishers Inspection Annual inspection and tagging of (22) portable fire extinguishers and (5) wheeled extinguishers BRC ID: 500600
Below are the deficiencies following the recently completed annual inspection: Portable Extinguishers Repair (3) 50lb ABC Wheeled Units due for service 1. Behind Admin Building (Below) in Oil Storage Area. 2. Front of Unit 2 3. Front of Unit 4 (1999) Cylinders and no services on them. (1) 10lbs ABC due for Hydro in Admin switch gear. (1) 5lbs CO2 due for hydro in CEMS#1 (1) 5lbs CO2 due for Hydro in CEMS#2 (1) 5lbs CO2 due for Hydro in CEMS#3 (1) 100lbs CO2 Wheeled Unit Due for Hydro
Found wire with exposed wire about 3 inches. Also found heat detectors "t-tap". Rewired and reterminated all heat detectors in load tunnel. Check wires and manual pulls. Everything is fine.
Found wire with exposed wire about 3 inches. Also found heat detectors "t-tap". Rewired and reterminated all heat detectors in load tunnel. Check wires and manual pulls. Everything is fine.
Conducted annual fire extinguisher and emergency/exit light inspections
Annual inspection and tagging of (26) portable fire extinguishers and (5) wheeled extinguishers
Annual inspection of Fire alarm system in the Admin building
Annual inspection of Fire alarm system in the Admin building