Sprinkler Inspection Quarterly Fire Sprinkler Inspection Deficiency: Gauge - Need to replace all 11 gauges, there all older then 5 years of age Main drain Sign - Need to add (10) Main Drain signs, all are missing Control valve sign - Need to add (11) control valve signs, due to Missing Calc card - Need to add (11) calc card due to Missing. - It is assumed the residual pressure observed during the main drain test is sufficient for the demand of the sprinkler system. AFS is not able to verify the building is adequately protected without the original hydraulic design Backflow - Need to add (3) back flow address signs, due to Missing Inspector test - Need to replace (8) inspector test signs, due to faded. Bell sign - Need to replace (3) bell signs, can no read