FDC failed the hydro-static testing – leaks were present during the test meaning that the connection will not withstand high pressure and may fail during a fire. Replace FDC connections and retest the line after repair has been performed. NFPA 25 (13.8.1) Dry Electrical supply room: Add the missing spare sprinkler heads and spare head wrench in the spare headbox. NFPA 25 (5.4.1.5.4) The stock of spare sprinklers shall include all types and ratings installed and shall be as follows; Facilities having under 300 sprinklers – minimum of 6 spare sprinklers NFPA 25 (5.4.1.5.5) One sprinkler wrench as specified by the sprinkler manufacturer shall be provided in the cabinet for each type of sprinkler installed to be used for the removal and installation of sprinklers in the system. Replace the sprinkler heads that were damaged during the wall tear down by a bobcat. Dry Electrical supply room: Measurements were obtained to replace the dry pendents in the loading dock and locked entry