Deficiency for FACP BASEMENT MECH ROOM: FACP AND BOOSTER PANEL BATTERIES ARE DUE FOR REPLACEMENT THIS YAER. THE BOOSTER PANEL ALSO NEEDS BATTERY TERMINAL CLIPS DUE TO CORROSION. CUSTOMER WOULD LIKE A QUOTE PLEASE. Suggested: 5 smoke detectors all lower-level read maintenance dirty on panel. Spoke with Kat the manager she would like a quote for cleaning. I mentioned you may want to have the rest of the basement smokes cleaned or possibly all Smokes on site since they have probably never been cleaned and more will possibly start showing up dirty on panel which takes longer for them to trip in an emergency situation. smoke detectors showing dirty on panel are as follows #7 lower-level banquet room East #8 lower-level banquet room Northeast #10 lower-level stairs to Kitchen #12 lower-level banquet room West #13 lower-level banquet room Southwest