2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Local Reviews
for clarkston, mi

Rated 5.0 out of 5 stars based on 3 customer reviews

Excellent service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

The rep that services our system is always so nice and professional.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Reliable Service

They have used Fire Pros for a while now at my place of work. They are very reliable and pleasant to work with. Dan was very thorough and expedient when he recently visited to inspect our fire extinguishers.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for clarkston, mi

Alex R.

Alex R. Job Checkin

Completed annual Fire Extinguisher inspection for 2020


George S.

George S. Job Checkin


Gerald R.

Gerald R. Job Checkin


George S.

George S. Job Checkin


Christian L.

Christian L. Job Checkin


George S.

George S. Job Checkin


George S.

George S. Job Checkin


Terrence  J.

Terrence J. Job Checkin


Alex R.

Alex R. Job Checkin

Completed annual Smoke/Co Alarm inspection for 2020


Christian L.

Christian L. Job Checkin


Alex R.

Alex R. Job Checkin

Retested Horn/Strobes after FACP Replacement found additional issues and wrote up Deficiencies for new service provider.


Alex R.

Alex R. Job Checkin

Replaced NAC PNL B2-5 In Hallway by A216 Above Drop Ceiling (Existing Old Notifier FCPS-24 was in trouble on FACP / after further Trouble Shooting found That Out-put 1 was Fried and was not recognizing loop or end of line resistance) Tested Horn/Strobes and Reset. system. ***Trouble Cleared off FACP*** Upon Arrival FACP also stated Supervisory LCD 80 (This Trouble is due to the remote Annunciators being removed due to construction) Work Approved by Scott Ballard


Alex R.

Alex R. Job Checkin

Replaced RTU-2 Supply (On-Roof) Duct Smoke Detector that was water damaged Wired, Tested and Reset. ***All Systems Normal and Reset***


Alex R.

Alex R. Job Checkin

Arrived on site FACP Showing ***All Systems Normal***Checked FACP History (Panel Shows Pre-Action System Trbl) Went To Boiler Room and checked Pre-Action System History. (History Showed System Low Battery/No Battery) Batteries we’re Bulging and Required Replacement. ***Replaced 2-12 volt 7 ah Batteries and Reset Date and Time ***All Systems Normal and Reset ***


Alex R.

Alex R. Job Checkin

Replaced 2-12 volt 18 ah batteries that failed load test ***All Systems Normal and Reset ***