6/1 LM/texted/emailed  reminding Paul of appt.  Paul confirmed  km 5/26/2021 - Paul approved the appointment for 6/2/2021 at 8:30am. Christian (Mgr) will be there. RP 5/19/21  Called Paul and Reminded him of the Appointment   SM 5/14/21  confirmed with Paul  for Thursday  5/20/21  sM 2/9/21 called and left VM for Paul. SM Portable Extinguishers and Kitchen Suppression Inspection Annual Fire Extinguisher Inspection (4 FE?) Semi-Annual Kitchen Hood Fire Suppression System Inspection (Ansul 9gl) Deficiency: Electric non fuel source on first Henny Penny Fryer from the right. Electric non fuel source does not shut down during system actuation. The unit is plugged in outside of hood. Looks like electric power cord has been spliced together. Deficiency: Number of Systems failed : 1 Deficiency: R-102 Regulator, Expellant Hoses and Cartridge are out of hydro date. Inoperable Deficiency: Discharge warning device did not operate during system actuation. Deficiency: Scissor link holders need to b