TD 2.28.20 VM for Walt - Walt called back confirming 1p Kitchen Suppression Inspection Semiannual Kitchen System Inspection PyroChem PCL-460 (1)500 link (3)360 links (10)Nozzles Deficiency: Need to add detection over fryer Deficiency for Pyro Chem PCL 460 right of hood: Appliance line piping is galvanized. Galvanized pipe cannot be used with wet chemical suppression system. Deficiency for Pyro Chem PCL 460 right of hood: System tank is over flow points. Tank has a max of 15 flow points system is currently at 17 flow points.


Jim S.

Jim S. Job Checkin

Portable Extinguishers and Kitchen Suppression Inspection Annual Extinguisher Inspection (13)ABC (2)K Semiannual Kitchen System Inspection Ansul R102-S3 (3)360 links (6)Nozzles Ansul R102-S3 (2)360 links (3)Nozzles Deficiency for R-102 3G right of hood: Deep fryer under main hood is undetected. TD 3.2.20 Fabian confirmed reschedule 2/24-Fabian confirmed the semi-annual kitchen suppression inspection/aware of alarms NW


Chris W.

Chris W. Job Checkin


Alex R.

Alex R. Job Checkin

Replaced 3 Heat Detectors that were Deficient from Recent Inspection (kitchen,Laundry Room,Basement HD’s) Tested And Reset System ***All Systems Normal and Reset ***


Alex R.

Alex R. Job Checkin

Replaced FACP battery that was Deficient from recent inspection ***All Systems Normal and Reset ***


Alex R.

Alex R. Job Checkin

Completed Annual Fire Alarm Inspection for 2019


Alex R.

Alex R. Job Checkin

Replaced Popeyes rear door pull station ***All systems normal and reset ***


Alex R.

Alex R. Job Checkin

Trouble shooted system Part required, will return